BuildFlo

BuildFlo Design Guide · Ventilation · Approved Document F

Dwelling ventilation design under Part F

Whole-dwelling and room extract rates under Approved Document F. MVHR, MEV and trickle vent guidance with built-in calculators.

Approved Document F 2021 Volume 1 sets minimum ventilation for new and materially altered dwellings in England. Wales and Scotland have aligned but not identical requirements - check the jurisdiction.

For MEP engineers on residential schemes, Part F drives whole-dwelling continuous rate, intermittent extract, and background ventilator provision.

Whole-dwelling continuous ventilation (Table 1.2)

AD F gives a rate by bedroom count, checked against 0.3 l/s per m² of internal floor area - use the higher value.

BedroomsMinimum continuous rate
113 l/s
217 l/s
321 l/s
425 l/s
529 l/s

Example: A 2-bed flat at 80 m² → Table gives 17 l/s; floor-area check gives 0.3 × 80 = 24 l/s → 24 l/s governs.

Part F / MVHR duty

Table 1.2 + 0.3 l/s per m²

Whole-dwelling continuous ventilation rate.

More ventilation tools →

Intermittent extract (Table 1.1)

RoomMinimum extract
Kitchen ( adjacent to hob )30 l/s ( or 60 l/s cooker hood )
Kitchen ( no hob adjacent )15 l/s
Utility15 l/s
Bathroom15 l/s
Sanitary accommodation6 l/s

Boost switches or automatic boost on kitchen/bathroom extract are required when using centralised continuous systems ( MVHR/MEV ).

System types - quick decision guide

  • System 1 - Background ventilators + intermittent extract - Trickle vents + bathroom/kitchen fans. Common on small refurbishments.
  • System 2 - Passive stack - Restricted; specialist design.
  • System 3 - Continuous MEV - Centralised or decentralised extract; make-up air via trickle vents.
  • System 4 - MVHR - Balanced supply/extract with heat recovery. Typical on new-build flats and Passivhaus-aligned schemes.

MVHR units are sized on the continuous duty. Ductwork is sized for that flow plus boost on extract branches.

Duct sizing check

Velocity and pressure drop for a circular duct.

Full duct calculator →

Checklist before you issue

  • Whole-dwelling rate meets Table 1.2 and 0.3 l/s per m²
  • Kitchen and bathroom extract rates to Table 1.1
  • Trickle equivalents if not using MVHR throughout
  • Acoustic limits for fans ( AD F Section 1.23 )
  • Commissioning and user handover information scheduled

---

*BuildFlo's ventilation calculator applies AD F Table 1.2 and the floor-area minimum automatically.*

Frequently asked questions

What ventilation system type should I use in a new dwelling?
System 4 MVHR is common on new-build flats and efficient dwellings. System 3 MEV with trickle vents suits simpler schemes. Check AD F system descriptions.
How do I size MVHR for a flat?
Use the higher of AD F Table 1.2 (by bedrooms) and 0.3 l/s per m² floor area. Allow boost on kitchen and bathroom extract branches.
What acoustic limits apply to ventilation fans?
AD F Section 1.23 sets maximum sound levels for continuous ventilation. Select fans with published SFP and acoustic data at design duty.

Related calculators