BuildFlo Design Guide · Ventilation · Approved Document F
Ventilation rate calculator for UK dwellings
Whole-dwelling and room extract rates under Approved Document F. Free Part F ventilation calculator for MVHR, MEV and extract fan sizing.
What this calculator does
Ventilation rate helps UK building services engineers with part f dwellings, occupancy (l/s per person), and space-type / ach rates. The calculation follows Approved Document F methods used in everyday MEP design — enter your project inputs below for a first-pass result.
Whether you searched for "ventilation rate", "ventilation rate calculator", or "how to ventilation rate", this page gives you a working tool plus the context to use it on a real job.
When to use it
Use this for early-stage sizing and sanity checks on UK building services work. It is not a substitute for issued calculations — verify against the project specification, drawings, and relevant standard before sign-off.
How to use it
1. Fill in the inputs for your scenario (defaults are starting points only). 2. Click Calculate — results include the method and assumptions where applicable. 3. Verify against the project specification and relevant standard before issuing.
Typical output unit: l/s.
Tips
- Defaults are indicative — replace with project-specific values from the architect, structural, or MEP spec.
- For issued calculations, save results in your BuildFlo project and attach to the calculation folder.
- Need the regulation citation? Open BuildFlo chat in the app and ask about ventilation rate under UK standards.
---
*Sign up for BuildFlo for the full calculator suite, saved results, and project workspace.*
Frequently asked questions
- What is the minimum whole-dwelling ventilation rate under Part F?
- AD F Table 1.2 gives a rate by bedroom count, checked against 0.3 l/s per m² of internal floor area — use the higher value.
- What extract rates apply to kitchens and bathrooms?
- Table 1.1 sets minimum intermittent extract: typically 30 l/s adjacent to a hob, 15 l/s for bathrooms, and 6 l/s for sanitary accommodation.
- Should I size MVHR on ACH or Part F tables?
- Whole-dwelling MVHR/MEV continuous duty is sized from AD F Table 1.2 and the floor-area check — not from an ACH formula.
Related calculators
- VentilationMVHR sizingSize mechanical ventilation with heat recovery — supply and extract flow rates under Part F. Free UK MVHR sizing calculator.
- VentilationDwelling ventilationWhole-dwelling and room extract rates under Approved Document F Volume 1 - MVHR, MEV, trickle vents, and kitchen/bathroom boost.
- VentilationDuct sizingCheck duct velocity, Pa/m, equivalent diameter and sound power from airflow. Free UK duct sizing calculator for circular and rectangular ductwork.
- VentilationHeat recovery tempCalculate MVHR/HRV supply air temperature from heat exchanger efficiency. Free heat recovery temperature calculator.