BuildFlo Design Guide · Thermal · CIBSE Guide A / Part L
Temperature design for UK building services
Design temperatures for UK offices, classrooms and plant rooms. Built-in room heat loss calculator with Part L fabric U-values.
Choosing the right design temperature is one of the first decisions on any heating or cooling job. Get it wrong and you oversize plant, miss comfort targets, or fight the client over setpoints later.
This guide lists typical internal design temperatures by room type, then walks through a single-room heat loss using Part L notional fabric U-values - the sort of first-pass check you do before opening a full SAP or dynamic model.
Design temperatures by room type
Pick a room in the calculator below to apply its design temperature automatically. Values are indicative - confirm against the project brief, UK design guidance, BB101 (schools), or HTM (healthcare).
| Room type | Category | Winter heating | Summer ( cooled ) | Typical ACH |
|---|---|---|---|---|
| Living room ( dwelling ) | Domestic | 21°C | - | 0.5 |
| Bedroom ( dwelling ) | Domestic | 18°C | - | 0.5 |
| Kitchen ( dwelling ) | Domestic | 21°C | - | 1.0 |
| Bathroom ( dwelling ) | Domestic | 22°C | - | 1.5 |
| Open-plan office | Commercial | 21°C | 25°C | 1.0 |
| Meeting room | Commercial | 21°C | 24°C | 1.0 |
| Reception / foyer | Commercial | 19°C | 26°C | 0.8 |
| Corridor / circulation | Commercial | 17°C | - | 0.5 |
| WC / changing | Commercial | 19°C | - | 1.5 |
| Classroom | Education | 20°C | 26°C | 1.0 |
| Retail sales | Retail | 20°C | 25°C | 1.0 |
| Sports hall | Leisure | 17°C | - | 1.5 |
| Plant room | Plant | 12°C | - | 0.5 |
| Server / comms room | Plant | 20°C | 22°C | 2.0 |
| Store / cupboard | Commercial | 16°C | - | 0.3 |
External winter design temperature for this demo: −4°C ( UK screening value - use UK design guidance for your site ). ΔT = internal design temp − external temp.
How the heat loss calculation works
1. Fabric loss on each surface: Q = U × A × ΔT ( W )
- Walls = gross wall area minus window area
- Roof and floor = plan area ( length × width )
- Glazing = window area you enter
2. Ventilation loss: Q = ρ × cp × V̇ × ΔT where V̇ = ACH × room volume / 3600
3. U-values in the demo are Part L notional dwelling fabric ( indicative for new-build screening ):
- Wall 0.18 · Roof 0.13 · Floor 0.15 · Window 1.4 W/m²K
- Part L limiting values ( England 2021 ): wall 0.26 · roof 0.16 · floor 0.18 · window 1.6 W/m²K
On a real project, replace these with the architect's issued U-values from the specification - never size final plant on notional defaults alone.
Extended reference - non-domestic setpoints
| Space type | Winter heating | Summer cooling ( where provided ) |
|---|---|---|
| Open-plan office | 21-22°C | 24-26°C |
| Meeting room | 21°C | 24°C |
| Reception / foyer | 18-20°C | 26°C |
| Corridor / circulation | 16-18°C | - |
| WC / changing | 18-21°C | - |
| Plant room | 10-16°C ( frost protection ) | Ventilation only |
| Server / comms room | 18-20°C | 18-24°C ( equipment-led ) |
| Classroom | 20°C ( BB101 ) | Passive / limited cooling |
| Retail | 19-21°C | 24-26°C |
| Sports hall | 16-18°C | Natural ventilation often sufficient |
Domestic dwellings - Part L and SAP assume around 21°C in living areas and 18°C in bedrooms for annual energy modelling.
How to use these on a job
1. Confirm the brief - Cat A vs Cat B, client ESG targets, and BREEAM/WELL may tighten bands. 2. Check the standard - Schools: BB101. Healthcare: HTM/HBN. Offices: UK design guidance Table 1.5. 3. Size on design external conditions - UK design guidance external winter/summer design for your location. 4. Allow for diversity - Not every zone calls simultaneously; apply load diversity sensibly. 5. Document your assumption - Note the design temp on calculations and drawings.
Common mistakes
- Using 21°C everywhere including plant rooms, storerooms, and corridors - oversizes the system.
- Ignoring metabolic rate in sports halls, gyms, and kitchens - higher internal gains.
- Mixing up operative vs air temperature when the client specifies one or the other.
- Sizing on Part L notional U-values when the project spec has better ( or worse ) actual build-ups.
- Forgetting setback - night/weekend temperatures affect annual energy, not peak plant size.
---
*Need the full standard citation? Ask BuildFlo in the app - it indexes UK design guidance and Part L.*
Frequently asked questions
- What design temperature should I use for an office?
- Typical winter heating setpoint is 21°C for open-plan offices. Summer cooling where provided is often 24–26°C — confirm against the project brief and CIBSE Guide A.
- How do I calculate room heat loss?
- Sum fabric losses (U × A × ΔT) plus ventilation loss from air change rate and room volume. Use design external temperature for your UK location.
- What U-values should I use for a heat loss check?
- Use the architect's issued U-values from the specification. Part L notional values are for screening only — not for final plant sizing.